Effect of temperature on the cyclic fatigue resistance of thermally treated reciprocating instruments.

OBJECTIVES: The aim of this study was to evaluate the impact of body temperature on the cyclic fatigue resistance of different NiTi alloys used for the manufacturing of Reciproc Blue R25 (RB 25.08; VDW, Munich, Germany), X1 Blue File 25 (X1 25.06; MK Life Medical and Dental Products, Porto Alegre, Brazil) and WaveOne Gold Primary (WOG 25.07; Dentsply Maillefer, Ballaigues, Switzerland).

MATERIALS AND METHODS: Sixty instruments of the RB 25.08, X1 25.06 and WOG 25.07 systems were used (n = 20). Cyclic fatigue tests were performed at room temperature (20° ± 1 °C) and at body temperature (37° ± 1 °C). The instruments were reciprocated until fracture occurred in an artificial stainless steel canal with a 60° angle and a 5-mm radius of curvature. The time to fracture (TTF) was recorded. Also, the number of cycles to fracture (NCF) was calculated. Data were analysed using one-way ANOVA and Tukey's tests for inter-group comparison at both temperatures and for the reduction of cyclic fatigue at body temperature. For intra-group comparison at the different temperatures, the unpaired t test was used.

RESULTS: The cyclic fatigue test at 20 °C showed that RB 25.08 and X1 25.06 presented significantly higher TTF and NCF than WOG 25.07 (P < 0.05). At 37 °C, all groups presented significant reduction of TTF and NCF (P < 0.05). RB 25.08 presented significant higher TTF than WOG 25.07 (P < 0.05). Regarding the NCF, there was no significant difference among the groups (P > 0.05). The WOG 25.07 presented the lowest percentage reduction of cyclic fatigue (P < 0.05).

CONCLUSION: The body temperature treatment caused a marked reduction of the cyclic fatigue resistance for all reciprocating instruments tested. The RB 25.08 and X1 25.06 systems presented similar results at both temperatures tested. However, WOG 25.07 presented the lowest percentage reduction in fatigue resistance at body temperature.

CLINICAL RELEVANCE: The cyclic fatigue resistance of NiTi reciprocating instruments has been evaluated at room temperature. However, the fatigue resistance significantly decreases upon exposure to body temperature, which could affect the mechanical behaviour of the NiTi instruments during root canal preparation.

Full text links

We have located links that may give you full text access.
Can't access the paper?
Try logging in through your university/institutional subscription. For a smoother one-click institutional access experience, please use our mobile app.

Related Resources

For the best experience, use the Read mobile app

Mobile app image

Get seemless 1-tap access through your institution/university

For the best experience, use the Read mobile app

All material on this website is protected by copyright, Copyright © 1994-2024 by WebMD LLC.
This website also contains material copyrighted by 3rd parties.

By using this service, you agree to our terms of use and privacy policy.

Your Privacy Choices Toggle icon

You can now claim free CME credits for this literature searchClaim now

Get seemless 1-tap access through your institution/university

For the best experience, use the Read mobile app