We have located links that may give you full text access.
Highly efficient combustion with low excess air in a modern energy-from-waste (EfW) plant.
Waste Management 2018 March
The effect of low excess air and high adiabatic combustion temperatures on CO and NOx formation has been investigated on a commercially operated energy-from-waste plant. With optimal combination of low O2 levels and stable combustion control, uncontrolled NOx levels could be lowered to 100-150mg/Nm3 (dry, at 11% O2 ) while keeping CO emissions at low levels. Even at adiabatic temperatures above 1400°C thermal NOx hardly contributed to the total NOx emissions in a grate-fired EfW plant. An advanced combustion control system allowed continuous operation with very little excess air (λ<1.2) while keeping CO and NOx at levels well below the legal emission limits.