We have located links that may give you full text access.
Evaluation Studies
Journal Article
[Evaluation of chlorine dioxide concentrations needed to effectively control contamination by Legionella spp in hospital hot water distribution systems].
Igiene e Sanità Pubblica 2016 March
This aim of the study was to identify effective levels of ClO2 for control of Legionella spp. contamination in the hot water (45-55 °C.) distribution system of a 579-bed hospital in Ravenna (Italy). Overall, 663 hot water samples were collected from the hospital's sinks and shower taps and were analyzed. Trend line analysis, which describes the trend in the number of positive samples collected according to disinfectant concentration, shows that the lowest number of positive samples was achieved with concentrations of ClO2 between 0.22 and 0, 32 mg /l.
Full text links
Related Resources
Get seemless 1-tap access through your institution/university
For the best experience, use the Read mobile app
All material on this website is protected by copyright, Copyright © 1994-2024 by WebMD LLC.
This website also contains material copyrighted by 3rd parties.
By using this service, you agree to our terms of use and privacy policy.
Your Privacy Choices
You can now claim free CME credits for this literature searchClaim now
Get seemless 1-tap access through your institution/university
For the best experience, use the Read mobile app